k-06 is capacity type level transmitters. The probe is based on properties of capacitor. Vessel wall & probe forms two electrodes. If vessel is of non conductive material, the probe will be double rod type. The distance between electrode & surface area of electrodes remain unchanged. The variable is the depth of the material being measured which represents the dielectric constant between two electrodes. Air and vacuum have relative dielectric constant as I & that of liquids, it is grater than I. The capacitance of the capacitor therefore depends on how much material lies between the prob & vessel wall i.e whether the probe is covered with or free from material. The capacitor changes with change in level of the material & provides corresponding 4-20 mA DC continuous output.
Probe Length | 1 ) upto 2 mtr. - Rod type 2 ) From 6 mtr. 15 mtr. - Rope type |
Type of Output | 1 ) 4 to 20 mA DC, 2 wire 2 ) 0 – 5 V DC |
Accuracy | +/-1% F.S |
Linearity | +/-1% |
Process Temperature | 100°C max |
Process Pressure | 10 kg/cm2 max |
Probe MOC | SS 316 |
Power Supply | 24 V DC, External |
Power Consumption | < 6 VA |
Response Time | < 1000 mSec |
Temperature Coefficient | +/-1% per 0C |
Transmitter Enclosure | Flame-proof, IP-65, IIA, IIB, CMRI Certified |
Process Connections | 1 ) I" BSP Threaded 2 ) I" ASA 150, Flanged |
Mounting | Top of the tank |
Operating Conditions | Temperature 0 to 55°C Humidity 5 to 95% non condensing |
OPTIONAL | |
Local Display | 8 x I LCD ( 4 digit indication for Level) |
Note: Process temperature & pressure exceeding specified limits, kindly consult with factory